text.skipToContent text.skipToNavigation

Protecta*Lite Arrester (106 kV MCOV)

By OHIO BRASS 

Catalog ID: 602106A2X4001

By OHIO BRASS
Catalog ID:  602106A2X4001
This web listing represents a sampling of typical configurations. Protecta*Lite Arrester assemblies can be customized for all distribution and transmission lines.

Selection of arrester MCOV size is based upon the maximum continuous voltage that is applied across the arrester in service (line-to-ground). For arresters on effectively grounded neutral systems, this is normally the maximum line-to-ground voltage

Example: 84 kV on a 138 kV system. For ungrounded or impedance-grounded systems, the MCOV should be at least 90 percent of maximum phase-to-phase voltage.

For more information about arrester selection, please contact your Hubbell Power Systems representative.

Transmission line arrester to improve system performance and reduce interruptions

  • Eliminate lightning interruptions with Protecta*Lite Arresters
  • Custom designs available up to 765 kV
  • Protecta*Lite Arresters offer protection on both shielded and unshielded lines
  • To learn more about how Protecta*Lite improves line performance, click here to visit our blog.

More Options

Product Details

General

Application Above 35 kV
Type Line Arresters
UPC 096359489788

Electrical Ratings

Creep and Leakage Distance 176.5 in (4483.1 mm)
Duty Cycle 132 kV
Frequency Rating 48-62 Hz
MCOV 106 kV
Maximum .5 Microsecond Discharge Volts @ Classifying Current 424.2 kV
Maximum Discharge Voltage
  • 317.8 kV @ 1.5 kA
  • 338.8 kV @ 3 kA
  • 359.1 kV @ 5 kA
  • 394.8 kV @ 10 kA
  • 444.4 kV @ 20 kA
  • 528.5 kV @ 40 kA
Maximum Switching Surge Protective Level @ 500A 304.5 kV
Pressure Relief Capability-Symmetrical rms (kA) 20
Voltage - Line 161 kV

Certifications and Compliance

Industry Standard(s) IEEE/IEC

Resources and Downloads

Videos

Hubbell Power Systems Metal Oxide Varistor (VI01022E0718)

Ohio Brass Protecta*Lite® Systems Surge Arresters (VI01020E0118)